Does your portable air conditioner not blow cold air when it is running?
This is a very frustrating situation that homeowners are used to, particularly in hot summers. Your portable AC is turned on and everything seems to be working (fan blowing, lights on) but the air is not cooling, what could be the reason?
It may be as easy as user settings, mechanical, or environmental.
We have listed the most frequent causes and their possible solutions in a table below, and then in detail how to diagnose and solve the problem.
| Common Cause | Possible Solution | 
|---|---|
| Thermostat or mode set incorrectly | Set to Cool mode and a temperature lower than room temp; ensure thermostat sensor is working | 
| Dirty or clogged air filter | Clean or replace the filter to restore airflow and cooling | 
| Blocked exhaust or poor ventilation | Clear obstructions; straighten and shorten the exhaust hose for proper hot air venting | 
| Refrigerant leak or low refrigerant | Requires professional repair; often more cost-effective to replace the unit if older | 
| Frozen evaporator coils | Turn off AC to defrost; address underlying airflow or refrigerant issues before restarting | 
| Room too large or heat load too high | Use appropriately sized AC (higher BTU) or improve room insulation and shading | 
| Poor maintenance (dirt, water, etc.) | Perform regular maintenance: clean filters/coils, drain water, and ensure unit is level | 
Thermostat and Settings Issues
One of the leading causes of a portable AC running without cooling is incorrect thermostat settings or control problems. The first is to make sure that the unit is indeed on cooling mode. Most portable air conditioners can be set in several modes (Cool, Fan, Dehumidify, etc.).
It might be set on accident to only Fan or Dry, and the compressor will not turn on, so there will be no cold air. Make sure that the mode is on cool and the desired temperature is less than the room temperature. When the thermostat is set too high (say at 78°F when the room is 80°F), the unit may not turn on cooling or will turn off soon, so it will not feel like it is blowing cold.
It could also be that the thermostat sensor within the unit is giving a wrong reading of the temperature. Portable ACs use a sensor (usually behind the air intake) to measure the temperature in the room.
In case that sensor is defective or is subjected to cold air of the unit itself, it may believe that the room is cool enough and turn off the cooling. As a troubleshooting measure, set the thermostat to a significantly lower temperature (e.g. 60°F) and see whether the compressor turns on. Ensure that the sensor (if available) is correctly placed close to the evaporator coil but not touching it (this is a suggestion to room AC units). Avoid placing the unit in direct sunlight or in a place that will cause the thermostat to be fooled by heat.
The other setting to be checked is the fan speed. The majority of portable air conditioners have the possibility to change the fan speed. The evaporator may become too cold (because of low airflow) and may freeze up when the fan is run at very low speed in a very humid room.
Coil freezing in humid conditions and poor distribution of cooling can be avoided by increasing the fan speed. Also make sure that some timer is not accidentally switching off the compressor. An active timer may switch the unit off earlier than anticipated, as one manufacturer observes, and it may appear that the unit will not remain cooling .
Don’t Overpay for HVAC Services – Call 888-894-0154 Now to Compare Local Quotes!
Cooling problems may also be a disguise of power supply problems. When the AC is on (fan is on) and the compressor fails to start, then it might be electrical.
As an example, low voltage to the unit (which is usually due to a long extension cord or an overloaded circuit) may not allow the compressor to engage. Never use an extension cord with these units, and plug the portable AC directly into a well-rated outlet (most need a dedicated 120V/15A circuit). When the outlet or circuit is not able to provide sufficient current, the motor of the compressor may not be able to work or a safety cutoff can be triggered. Also, make sure that the plug and cord of the unit are not damaged and the circuit breaker has not tripped partially (although, in case the fan is working, the power is available, but low voltage is still a possibility). There is a reset button on the plug of some units (a built-in circuit breaker/GFCI); check that it is not tripped.
In case you think it is an internal electrical problem (a bad control board or a bad capacitor that aids in starting the compressor), these are more difficult to diagnose without a professional tool.
The surest indication of a bad compressor capacitor is when the compressor attempts to come on (you may hear a hum or flickering lights) but then quits, but the fan keeps on running. At that, you will require a technician to fix it. But before concluding to that, eliminate simpler causes as explained below.
Clogged Air Filter Reducing Cooling

One of the most common reasons why a portable AC fails to cool the room is a dirty or clogged air filter. The filters contained in portable units can be washed and they capture dust and debris in the air.
Failure to clean the filter regularly may choke it with dust thereby limiting the flow of air. Less airflow implies that the evaporator (the cooling coil) is not receiving sufficient warm air blowing over it. This may create two issues: the AC will not be able to cool the room (not enough warm air is being cooled), and the evaporator coil may become too cold and freeze up because of the absence of warm air, which will only worsen the cooling.
Inspect the air intake filter of your AC (which is typically located behind or at the side of the unit, and requires the removal of a panel). In case it appears to be dirty or clogged, clean it as soon as possible. The majority of portable AC filters are reusable: you can vacuum the dust off or wash the filter with warm water and mild detergent, dry it thoroughly and reinstall it .
When filters are used heavily, they may need cleaning as frequently as once a week (one manufacturer suggests weekly cleaning to maximize performance) . At least, check the filter every two weeks . A clean filter will guarantee the airflow, which is essential to blow cold air by the unit.
Cleaning the filter does not only restore the cooling performance but also avoids other problems. A dirty filter may result in overheating of the compressor or freezing of the evaporator coil. Actually, clogged filters and coils have been reported to lead to system failure and even premature compressor failure in case they are not addressed .
Therefore, this easy maintenance procedure can spare you of greater troubles in the future.
In addition to the primary air filter, see whether your portable AC has any secondary filters or pre-filters (some have a separate filter to the condenser air intake). Make sure that the air passages are open.
When the filter is removed, use a flashlight to look inside the machine to determine whether the coils (evaporator or condenser) are dirty or dusty. In that case, clean them lightly (see more about coil cleaning in the Maintenance section). Getting the airflow back to normal usually restores the cold air and is a quick fix by the homeowner.
Blocked Exhaust Hose or Ventilation Problems

Portable air conditioners release hot air via an exhaust hose which is normally released through a window. When the exhaust hose is clogged, kinked or not properly installed, the unit will not be able to dispose of heat easily and you will experience minimal or no cooling.
In this case, the AC can be on and even cooling the interior but the heat is not getting out of the room. This may end up in a net zero cooling effect or even the AC blowing hot air since the hot exhaust is leaking back in.
Check the exhaust hose system: ensure that the hose is well connected at both ends (the AC unit and the window vent kit). The hose must be as short and straight as can be.
Do not have long extensions or unwarranted bends. The manufacturers usually recommend not to stretch the hose longer than its usual length (usually about 5 feet) since the longer hose or coiled up hose may hinder the airflow . As an example, Honeywell observes that excessive length of the hose or sharp bends may inhibit effective ventilation of hot air . In case of slack hose, squeeze it down to the shortest length which extends to your window . Make sure that the hose is not badly kinked or crushed behind furniture as well.
One of the problems is a kinked or incorrectly fitted exhaust hose, which may limit the release of hot air. Ensure that the hose is not kinked and as short as possible to ensure that the heat escapes.
Also, check the window vent panel. When the window bracket is not sealed properly, there is a possibility of hot air finding its way back to the room.
The panel should have little gaps around it; foam seals or weatherstripping should be used to make sure that the hot outdoor air does not enter and the hot exhaust does not enter the house at all. Similarly, in case you are using a ceiling vent or a sliding door kit, seal any openings. Basically, you do not want the hot air to recycle back or to draw more heat.
The surrounding of the unit may also be poorly ventilated. The portable AC draws room air into it to cool the condenser (particularly single-hose models) and when it is pushed against a wall or cluttered around, the intake can be deprived of air.
Don’t Overpay for HVAC Services – Call 888-894-0154 Now to Compare Local Quotes!
Ensure that there is sufficient space around the unit to allow air intake, normally at least 1-2 feet of free space (consult your manual). Make sure that the air intake and outlet vents are clear. As an example, do not hang curtains or put furniture directly against the inlet or outlet of the AC. A clogged intake may lead to overheating or poor cooling and a clogged cold air outlet will not allow the cool air to circulate into the room.
Another factor that has to do with ventilation is to ensure that the doors and windows in the room under cooling are closed. When windows or doors are left open, the cold air will flow out and be substituted by the warm air either outside or in other sections of the house, which will nullify the work of the AC.
Single-hose portable ACs, in fact, generate a little negative pressure (they ventilate indoor air) which can draw in warm air through cracks or open doors. To reduce this, make the cooled room as detached as possible with the hot areas. Lock the door and reduce the number of times it is opened. In case you can feel warm air coming in (e.g. through a door), a door draft stopper can be used. The more the room is tight, the more the cooling effect will be.
Low Refrigerant or Cooling System Issues
When the simple troubleshooting fails to fix the problem, then the refrigeration system of the AC might be faulty. The portable air conditioner will run but not cool when there is a leakage of refrigerant or low level of refrigerant.
Refrigerant is the blood of your AC cooling cycle, so when it has leaked out, the compressor can still be running but it will not be able to cool the evaporator coil properly. Consequently, the air that will blow out will be at room temperature or warm. An indication of low refrigerant is that the evaporator coil (or the space behind the filter) freezes up as discussed above. You may see frost or ice on the coil or condenser or even water dripping as the ice melts. The other indication is that the compressor turns off rapidly because of the pressure problems inside.
Regrettably, the average homeowner cannot fix refrigerant leaks on his or her own. They need to find the leak, fix it and refill the system with the right refrigerant, which should be done by certified HVAC technicians.
Fixing a refrigerant leak in a portable unit is prohibitive in many cases because of the cost and effort involved. (As a point of reference, a home air conditioner system can cost hundreds of dollars to repair and recharge, and this is close to the cost of a new portable air conditioner.) In case your unit is rather new and still has a warranty, you can address the manufacturer or a service center to find out whether it can be repaired within a warranty. Otherwise, when a leak is proved and the unit is out of warranty, you might be inclined to replace it instead of repairing it because of the cost.
What should you do to know that refrigerant is the cause? Assuming that you have checked that the filter is clean, the exhaust hose is in good condition, the ambient conditions are not extreme, and the compressor is certainly running (you can usually hear it hum when it is engaged), but the air is still not cold at all, then the problem is probably with the refrigerant.
Also, when the unit was cooling well but slowly lost its cooling ability over time (and is now blowing slightly cool or even warm air), this is an indication of a slow refrigerant leak. There are also users who report oily residue on or under the unit when there is a refrigerant leak, since the compressor oil may leak out with the refrigerant (this may not always be evident, but it is a clue when it is).
Compressor issues are of the same kind. The part that compresses the refrigerant gas is the compressor and it is a necessary part in cooling.
The AC will not cool in case the compressor breaks mechanically or electrically. You may hear the fan operating but the deeper hum of the compressor never comes on. Reasons may be a burned-out compressor motor, a bad start capacitor or an internal overload tripping. When a compressor is not running at all (otherwise the unit is powered up) it is usually a sign of an internal failure or a safety shutoff. As an example, on very hot days the high-pressure limit switch of the compressor may open and shut the compressor off to prevent damage (particularly when the condenser is unable to reject heat). At that, the compressor may try to restart when it cools down. Other times, it can be as simple as cleaning the filter and letting the unit rest to enable an overheated compressor to run again.
In the event that the compressor has actually failed (electrically open or seized) then the only remedies are to repair it professionally or replace the unit. Since replacement of compressors is extremely costly (usually close to the price of a new one) , replacement is normally more reasonable on a small portable AC unless it is under warranty.
To conclude, when it comes to refrigerant or compressor problems, homeowners are advised to consider the cost of repairing it thoroughly, as in most of the situations of cooling loss because of the problems with refrigerants or compressor, it may be more reasonable to plan an upgrade to a new AC.
Frozen Evaporator Coils

Frozen evaporator coil is an indication as well as a consequence of no-cool situations. When the coil (the part that gets cold) becomes frozen into a block of ice, the air cannot flow through it normally and the AC will blow little or no air, and what air does come out is not very cold, as the ice insulates the coil against the air.
This is found out by many portable AC owners when they are trying to find out why there is no cold air, and they may see frost or ice by looking behind the filter or see water puddles as the ice melts. Freezing may occur due to several reasons, the most common ones being low refrigerant or lack of airflow (or both). Ice on the coil will most often be caused by a dirty filter (airflow problem) or a refrigerant leak.
Don’t Overpay for HVAC Services – Call 888-894-0154 Now to Compare Local Quotes!
In case you see ice, the initial thing to do is to switch off the air conditioner. Allow it to defrost and dry up (you may place towels under the unit in case of melting ice water). Do not even chip the ice because you may break the coils.
In the process of thawing, check potential causes: Is the filter clogged (which might have led to the freeze)? Is the fan not blowing hard (fan failure may result in freeze due to no airflow)? Is the room very moist or was the AC at a too low temperature? Humidity may also cause icing since more moisture will be frozen on the coil and this is likely to happen when the coil drops below 32°F. Once the ice is melted, wash the filter and then leave the AC to run on fan-only mode to dry the remaining moisture.
After everything is clear, attempt to run the unit once again and see whether it cools. In case it freezes again, then there is probably a more serious problem like low refrigerant or fan speed/thermostat problem.
You might require a specialist to inspect the level of refrigerants or the compressor condition. Conversely, in the event that the freeze was a fluke (perhaps because of temporarily low airflow, or an unusually humid day), then your cleaning and reset may be all that is necessary. To avoid coil freeze in the future, keep the filter and coils clean, do not set the thermostat unreasonably low (do not go much below ~70F, especially in humid weather) and make sure the fan is running at least at a moderate speed to keep air moving.
Electrical and Safety Considerations
Although we have mentioned some electrical problems in the thermostat section, it is worth making a few safety and electrical points, since sometimes an AC that is not cooling is actually an AC that is not running fully.
As an example, you may see lights going dim or hear clicking when the compressor attempts to start repeatedly and trips. This might be due to a power issue such as a bad capacitor or low power. When you feel something of this sort, it is prudent to seek the services of a professional. Do not open the sealed compressor or electrical parts yourself because you may get a shock and you may invalidate warranties. Rather, pay attention to the external and user-replaceable checks: filter, hose, drain, etc. When those fail to do it, then it could be an internal electrical fault.
Among the things to be checked is the presence of error codes on the indicator lights of the AC. Most newer portable ACs have self-diagnostic codes (such as E1 or E2) to report issues (such as sensor failure or full water tank (more on the water tank below).
In case any such code is shown, refer to the manual of your unit. It would be able to identify a faulty electrical sensor that is not allowing cooling.
Cooling can also be halted by water collection (condensate) problems. Portable ACs dehumidify the air in the process of cooling. In most designs, that water is either evaporated out the exhaust or gathered in an internal tank or tray.
In case your unit has a tank and it fills up, most models will turn off the compressor (and in some cases the fan as well) to avoid overflow. In other instances, the fan may keep on running without cooling as a form of warning. See whether your unit has a water full indicator light; in that case, all that might be required is to drain the tank and start cooling again. Although there is no indication, it is good to drain the unit periodically especially when you are in a very humid place. Find the drain plug (the bottom rear of the unit) and drain any water collected into a pan or bucket . It is always safe to switch off and unplug the AC before draining. The level of the unit is also significant to drainage, in case it is tilted, the water may not drain correctly and activate a sensor.
Once you drain the water, you will hear the compressor kick back in most of the times after the internal float switch resets. In case your model supports it, the continuous drain option (a small hose is attached to the drain spout to direct water to a floor drain or bucket) will help ensure that the unit never stops because of a full tank.
Also, it is good to run the AC in fan mode 10-15 minutes after prolonged cooling to dry the coils and reduce the amount of remaining moisture, which is particularly good before storing the unit (to prevent mold).
External Factors: Room Size, Heat Load, and Humidity
In some cases, your portable air conditioner might not be faulty in any way at all, but the problem might be in the external conditions that are beyond the capacity of the unit. The portable ACs are usually meant to be used in small and medium-sized rooms.
When you are trying to cool a room that is too big or has a lot of heat load, the unit might be running all the time and still never cool the air down. The AC may be blowing cool air but the room condition overrides it and you feel that there is no cooling or minimal cooling. So, what are the main aspects here?
- Size of the room and BTU: All portable ACs are rated in BTU (cooling capacity). In case your room has a square footage and heat gain that needs 12,000 BTUs and you are using an 8,000 BTU unit, it will not perform well. It can keep running without attaining the desired temperature. Undersizing a unit will not allow it to maintain the room cool enough as Haier observes. Conversely, an over-sized unit may short-cycle and switch off prematurely, but when it comes to not blowing cold air, the problem is actually undersizing. Look at the suggested room size of your type of AC (usually in the manual or product specs). In case your room is bigger, it is a probable cause of poor cooling. The cooling load is increased by the number of windows, exposure to sunlight and even the number of occupants in the room, so take them into consideration. In case it is the capacity problem, you might want to get a more powerful unit or install an additional AC in the area.
- High ambient temperatures: Portable ACs can only work up to a certain level of ambient temperatures. When it is very hot (say 95F+ outside) and the room was already hot, then the unit must work harder. The condenser may even overheat and some units may even switch off. Give it a hand by drawing blinds/curtains to shut out sun , and perhaps running a fan to move air.
- Bad room insulation or open spaces: In case the cooled room is not well insulated, has a lot of air leakage or is open to other rooms, then the cooling will not be sufficient. As an example, a portable AC will have an uphill task cooling a kitchen with running appliances or a room with high ceiling and open stairwell. Attempt to seal the cool air by sealing openings temporarily. Apply shades, weatherstripping or close doors of adjoining spaces. Insulated walls and carpeting will keep the cool air in and tile or concrete and uninsulated walls will cause the AC to work harder.
- High humidity: A room with high humidity will not be as cool as a room with low humidity since the AC will need to remove a large amount of moisture (latent heat) as well as cooling the air. You may not feel cool until the humidity is reduced. When it is very humid, the AC may also empty its condensate tank very fast (as discussed) or even become less efficient. When you realize that your portable AC is not cooling well during super humid days, make sure it is draining well. It is also possible to operate a standalone dehumidifier in advance or in parallel with the AC to lower the humidity load (some portable ACs have a dry mode that is a dehumidifier).
In a nutshell, make your AC environment friendly: seal the building, cover the windows, minimize the heat generating sources in the building, and think about the size of the unit. Portable units are most suitable in single rooms or additional cooling, they are not usually suitable in large open plan spaces or in multiple rooms. When used within its capacity, you are likely to feel a strong flow of cold air coming out of the unit and a gradual decrease in the room temperature.
In case the unit is operating in a correct environment and yet there is no cold air, then it is reasonable to revert to the mechanical problems mentioned above.
Troubleshooting Steps for Homeowners
With the potential causes discussed, the following is a brief step-by-step troubleshooting procedure that you can use. This will assist in the systematic diagnosis of the reason why your portable AC is not blowing cold air and solve it safely:
- Check settings: Check that the unit is plugged in and switched on (no error lights), in Cool mode and that the thermostat is set a few degrees colder than the current room temperature. At this point, set the fan speed to medium or high. This removes any easy setting supervision.
- Listen to the compressor: Listen to the compressor after the AC has been running a couple of minutes. You ought to hear the compressor come on with a low hum (not the sound of the fan). In case you do not hear it, the compressor might not be operating, and this indicates a problem with the thermostat, power, or mechanical problems. In case it is running, yet air is not cold, follow this list.
- Clean and check the air filter: Switch off and disconnect the AC. Take out the filter and wash it in case it is dirty. A layer of dust can be a big airflow blocker, even when it does not appear dirty. Also look at the evaporator coil (behind where the filter is) to see whether there is any ice or too much dirt. Clean the filter, allow any ice to melt and then run the unit again to determine whether cooling is improved.
- Exhaust setup: Ensure that the exhaust hose is well attached and not kinked or clogged. Touch the hose, is it warm when the AC is on (it must be, because it is moving hot air out)? When it is not warm at all, then the compressor may be not working. In case it is hot, and the room is not cooling, make sure that the hot air is not coming back inside. Close the window firmly around the panel and cover the gaps. It is also a good time to shut all the doors and windows in the room to avoid loss of cooled air.
- Check the conditions of the room: does the room have too much space or exposure to the sun compared to the BTU rating of your AC? When you have just turned on the AC on a hot day, be patient and assist it by closing curtains and reducing the heat sources. In case the room size is marginal to the unit, it is possible that you have to cut the load (cool only one room, not several areas).
- Empty water (where applicable): In case your model has a condensate tank and particularly when you live in a humid area, make sure that the tank is not full. When water has to be emptied, many units will go off cooling (compressor off) . Empty the water by the manual (normally through a small drain plug at the bottom). Once drained, reconnect it, turn it on and watch to see whether the compressor kicks in and the cold air comes back.
- Test and restore power: Once the above steps (filter clean, hose correct, water drained) have been done, turn the unit back on. Put it on low temperature and check whether cold air is released after some minutes. In many cases, a typical problem will be solved by one of the above actions.
- Watch out on icing or short cycling: Watch the unit over the next hour. When you observe that the airflow is again decreasing or the compressor is turning on/off too quickly, it may be a more serious problem such as low refrigerant or internal problem. This is where simple troubleshooting has been done.
- Contact a professional: In case none of the above has restored cooling, it is probably a mechanical/electrical issue (refrigerant leak, compressor failure, etc.) which needs professional assistance. Call an HVAC technician or the support line of the manufacturer in case the unit is covered by the warranty. Make sure you inform them of what you have already checked. It is not recommended to keep operating a unit that is not cooling because it may overload parts.
Safety should be in mind throughout the troubleshooting process. Clean filters or check internal parts by unplugging the unit. Do not touch refrigerant lines or wires. These guidelines will help homeowners to resolve most of the AC not cooling problems themselves.
The trick is to deal with the simple stuff (settings, filter, ventilation, drainage) and not to jump to the worst.
Maintenance Tips to Prevent Cooling Issues
In order to make sure that your portable air conditioner will keep blowing cold air throughout the summer, you need to maintain it regularly. The following are some of the measures that can be taken to avoid the frequent problems that result in loss of cooling:
- Keep the air filter clean: The air filter should be cleaned regularly as stressed. When you are using it heavily, wash or vacuum the filter at least twice a month (or even once a week in case you have pets or a lot of dust). Put it on your calendar so you do not forget. This maintains the airflow powerful and dust cannot clog the coils.
- Clean the coils and vents: Vacuum or dust the coils and vents: Every month or two, when the unit is unplugged, use a soft brush or vacuum attachment to gently clean the evaporator and condenser coils (if accessible). These coils get dirty and this affects the exchange of heat. Care should be taken not to break the fragile fins. It is also possible to blow out dust in the vents. Dirty coils can make the AC run inefficiently and overheat.
- Drain condensate: In case your AC does not evaporate all the water by itself, it is a good idea to check the drain pan or tank on a regular basis (daily during very humid weather). Empty it before it is full. This prevents any auto-shutoff because of high water level. In case you are not at home, install the continuous drain hose to a sink or drain and the unit will run without filling up.
How to Get the Best HVAC Prices
- Firstly, keep in mind that installation quality is always the most important thing for residential HVAC project. So never sacrifice contractor quality for a lower price.
- Secondly, remember to look up the latest rebates as we talked above.
- Thirdly, ask for at least 3 bids before you make the decision. You can click here to get 3 free estimates from your local contractors, and this estimate already takes rebates and tax credit into consideration and filter unqualified contractors automatically.
Lastly, once you chose the right contractor, remember to use the tactics from this guide: Homeowners Tactics When Negotiating with HVAC Dealer to get the final best price.




